AXIS TA1101-B Wiegand to OSDP Converter

Solution overview

The Wiegand to OSDP converter is used between the Wiegand reader and door controller to convert Wiegand data to OSDP. Each Wiegand reader must be connected to one converter.

Specifications

Product overview

  1. OSDP connector
  2. Wiegand LED
  3. OSDP LED
  4. Case open tamper
  5. Control button
  6. Wiegand connector
  7. DIP switch

LED indicators

OSDP LEDIndication
Blinks green every 1 sIdle. No OSDP communication
Blinks green every 50 ms on every OSDP response transmissionNormal OSDP communication
RedCasing tamper or Wiegand reader tamper is active
GreenIdle when the control button is pressed for less than 15 s
Blinks red/green every 250 msFlashing device software
Blinks green every 100 msRestore to factory default when the control button is pressed for more than 15 s (*)
Blinks red every 100 msErase the device software when the control button is pressed for more than 60 s (*)
Wiegand LEDIndication
Green
(On for 50 ms)
Wiegand data received
Green
(On for 1s)
Enter or exit the configuration mode (*)
Blinks green every 250 msIn the configuration mode (*)
RedWiegand output over current error

(*) See Control button.

Buttons

Control button

Connectors

OSDP connector

One 4-pin terminal block to connect to the OSDP reader.

FunctionPinNoteSpecifications
DC ground (GND)10 V DC
DC input (+12 V)2Supplies power to unit12 V DC, max 440 mA
A 3Half duplexRS485
B4Half duplexRS485

For more information, see electrical wiring drawings.

Wiegand connector

One 8-pin terminal block to connect to the Wiegand reader.

FunctionPinNoteSpecifications
DC ground (GND)10 V DC
DC output (+12 V)2Supplies power to reader. (Pass through from OSDP DC input)12 V DC, max 440 mA
D03Wiegand data0 to max 30 V DC
D14Wiegand data0 to max 30 V DC
LED 15Digital output0 to max 30 V DC, open drain, 100 mA
LED 26Digital output0 to max 30 V DC, open drain, 100 mA
TAMPER7Digital input or supervised input — Connect to pin 1 to activate, or leave floating (unconnected) to deactivate. To use supervised input, install end-of-line resistors. See connection diagram for information about how to connect the resistors. See Supervised inputs.0 to max 30 V DC
BUZZER8Digital output0 to max 30 V DC, open drain, 100 mA

For more information, see electrical wiring drawings.

Note

Wiegand data isn’t encrypted. To reduce security risk, install the Wiegand reader as close as possible to AXIS TA1101-B when using OSDP Secure Channel.

Supervised inputs

To use supervised inputs, install end of line resistors according to the diagram below.

Serial first connection

The resistor values must be 1 kΩ.

Note

It is recommended to use twisted and shielded cables. Connect shielding to 0 V DC.

DIP switch connector

6-pin terminal block. The default position of the DIP switches is OFF.

123456Description
OFFOFFAddress 0 (OSDP COMSET supported)
ONOFFAddress 1
OFFONAddress 2
ONONAddress 3
OFF120 Ohm RS485 termination disabled
ON120 Ohm RS485 termination enabled
OFFSingle Wiegand LED mode (LED1)
ONDual Wiegand LED mode (LED1 + LED2)
OFFCasing tamper disabled
ONCasing tamper enabled
OFFOSDP Secure Channel mode disabled
ONOSDP Secure Channel mode enabled

Troubleshooting

Reset to factory default settings

  1. Disconnect power from the product.

  2. Press and hold the control button while reconnecting power. See Product overview.

  3. Keep the control button pressed for 15 seconds. See LED indicators.

  4. Release the control button. The process is complete when the status LED indicator turns green. The product has been reset to the factory default settings.

Configuration mode

To enter the configuration mode, press the control button for more than 10 seconds until the Wiegand LED turns green for one second. See LED indicators. For how to configure supervised inputs, see Supervised inputs.

  • During the configuration mode:
  • Click the control button once to exit the configuration mode.

  • Click the control button twice to configure IO5 as digital.

  • Click the control button three times to configure IO5 as analog for supervised tamper.

  • Click the control button four times to configure the supervised open collector circuit.

  • Click the control button five times to configure the supervised switch circuit.

Upgrade the device software

Important
  • Preconfigured and customized settings are saved when you upgrade the device software (provided that the features are available in the new version) although this is not guaranteed by Axis Communications AB.
  • Make sure the device remains connected to the power source throughout the upgrade process.
  • Make sure you have an OSDP reader configured in your access control management system.
Note

When you upgrade the device with the latest version, the product receives the latest functionality available. Always read the upgrade instructions and release notes available with each new release before you upgrade the version. To find the latest device software and the release notes, go to axis.com/support/device-software.

  1. Download the device software file to your computer, available free of charge at axis.com/support/device-software.

  2. Log in to your door controller web interface as an administrator.

  3. Go to Peripherals > Upgrade > Upgrade converters.

  4. Click Upgrade converters.

  5. When the upgrade has finished, the product restarts automatically.

Technical issues, clues, and solutions

If you can’t find what you’re looking for here, try the troubleshooting section at axis.com/support.

Problems with the device software

Upgrade failure

If the upgrade fails, try upgrading the device software again.

No device software

If you press the control button during power on for more than 60 seconds, it is possible to remove the device software. To solve this, try upgrading the device software.

Contact support

If you need more help, go to axis.com/support.